SPD : USER GUIDE

※USER GUIDE

1. Check connector type, communication method and supply voltage to select suitable SPD type.

 

2. Grounding connection for SPD is input from part of the SPD and the shield part of the communication line should be connected to the grounding bus bar where <eca3G> is connected.

 

3. SPD should be installed close to the protecting equipment. If the SPD is installed over 30 meters away from the protection equipment, a secondary SPD should be installed near the equipment. Please try to make the cable length as short as possible.

 

4. <INPUT> of SPD is connected to the part where surges may occur, and <OUTPUT> of SPD is connected to the protecting equipment.

 

5. SPD should be installed in the protection box away from dust or rain.

 

6. All SPDs are designed to be maintenance free with its internal components not needing to be repaired, and designed so that the internal circuitry of the SPD will be disconnected (short) when a communication line is directly contacted with a power line as a result of an arc because of insulation breakage. Overcurrent may occur because of severe lightning.

 

7. If the internal part of the SPS is shorted, communication will be disconnected, and the SPD should be changed for reconnecting the communication. If the damage of the SPD is caused by a power line failure, the power line should be repaired.

 

8. SPD is a consumable product, it is advised to have a spare in the case of surge damage.

 

 

※ TYPE

No. Application Model Connector Line Nominal Line Voltage Max Line Voltage Protection Level Max Discharge Current
1 TEL/ADSL TLJ12C RJ11 1 150V 170V 220V 20kA
2 TLT32C 3p Screw 1
3 ISDN-T0 ISJ14B RJ11 1 48V 53V 70V 20kA
4 ISJ44B RJ45 2
5 IS3T4B 3p Screw 1
6 IS5T4B 5p Screw 2
7 LEASED/
4-20mA
LSJ12B RJ11 1 24V 28V 40V 20kA
8 LSJ42B RJ45 2
9 LS3T2B 3p Screw 1
10 LS5T2B 5p Screw 2
11 RS422/
RS485
RS3T6A 3p Screw 1 6V 10V 15V 20kA
12 RS5T6A 5p Screw 2
13 LAN LAJ46A RJ45 1 6V 10V 20V 20kA
14 CCTV/
ETHERNET
VIBP1B BNC-J/P   Bandwidth: 0~70MHz 10V 20V 20kA
15 VIBJ1B BNC-J/J
16 RF RFNP00 N-J/P Bandwidth:
0~1GHz
Power:
25~150W
Insert Loss: <0.5dB VSWR: <1.3 600V 20kA
17 RFNJ00 N-J/J
18 RFBP00 BNC-J/P
19 RFBJ00 BNC-J/J

CCTV System Lightning Surge Protection with

eca3G LP for Camera & Control Bo, eca3G LM for DVR, Monitor, Server,

Control System and Secure equi-Potential Environment